Funny pipe on one inch inlet rotors??

Post by Amosjdg »

Hey guys got a somewhat complex job going on. The area is roughly one acre of land. It will be using a 5hp booster pump to run 12-13 heads at a time at roughly 10 gpm. My question is this...is it a problem to use funny pipe. The smallest part of the line is 1 inch and the largest is 2 inch. The funny pipe fittings even with 3/4 fittings reduces down to to 1/2 at the elbow. Do you think it's a problem going from 1 inch line to 1/2 funny pipe back to 1 inch sprinkler? Will there be a significant volume loss restricting down to 1/2 inch at the sprinkler which has a 1 inch inlet?

Last edited by Amosjdg on Sat Jul 27, 2019 10:41 pm, edited 1 time in total.


User avatar

g-man
Moderator
Posts: 14697
Joined: Wed Jun 14, 2017 10:32 pm
Location: Fishers, IN
Grass Type: Front: NoMix Back: Bewitched
Lawn Size: 5678
Mower: John Deere 220E

Re: Funny pipe on one inch inlet rotors??

Post by g-man »

It all depends on the gpm at the heads, the length of funny pipe and the pressure your system has.


Topic Author

Amosjdg
Posts: 3
Joined: Sat Jul 27, 2019 9:13 pm
Location: California
Grass Type: Fescue
Lawn Size: 1 acre
Mower: Scag

Re: Funny pipe on one inch inlet rotors??

Post by Amosjdg »

System is sized for 10 gpm per nozzle a minute at 70 PSI. Guess I'm just wondering if I should go with a 3/4 inlet sprinkler instead of a 1 inch. Funny pipe won't be longer than 12 inches


Delmarva Keith
Posts: 966
Joined: Sat May 12, 2018 8:06 am
Location: Coastal Sussex, Delaware
Grass Type: TTTF
Lawn Size: 20,000
Mower: Bigs & Littles

Re: Funny pipe on one inch inlet rotors??

Post by Delmarva Keith »

Just from memory, 1/2" pipe way too small for 10 GPM. I think 1/2" is more like 5 and that was optimistic.

Rainbird publishes design guides that will step you through the calculations. For the main and start of the laterals you are talking about 130 GPM. A wrong choice and ending up undersized and you will be sorry. Either it won't work as intended or the fittings will erode as if sandblasted from the inside. Proper design will also help avoid oversizing the laterals as it goes down the line. At 130 GPM total, the potential cost saving of proper lateral sizing can be significant.

The system you're talking about should be engineered stem to stern. Take the time to do the math. For most typical residential systems, there's a lot of slop in the rule of thumb sizing everyone uses and plenty of room to have it all just work out in the end. In contrast, at around 130 GPM per zone, all the stuff everyone wants to ignore will be a factor. At those flow rates, ignore friction and velocity at your peril.

Last edited by Delmarva Keith on Sun Jul 28, 2019 7:09 am, edited 1 time in total.


User avatar

hsvtoolfool
Posts: 559
Joined: Mon Jul 23, 2018 4:29 pm
Location: Huntsville
Grass Type: Tifton 419
Lawn Size: 14K
Mower: Ego 21" + Ryobi 38" E-Rider

Re: Funny pipe on one inch inlet rotors??

Post by hsvtoolfool »

I agree 110% with @Delmarva Keith that you must do the math and verify that you won't have severe water hammer. Dems some big pipes and flow rates! You're definitely into the golf-course-pro-equipment realm with your GPM and pressure specs. Match the head inlet size to a rigid "swivel" swing joint riser. If the head has a 1" inlet, then use a 1" rigid swing joint.